Quad Amp Hardware Reference Manual

Getting Started

10

Heat Dissipation

The external mounting options (Opt3, Opt3A and Opt3B) allow the Quad Amplifier to be installed inside
a cabinet, with the Quad Amplifier heat sink mounted external to the cabinet or in an air plenum. In the
case of Opt 3B, provide good air circulation, in a plenum, with a minimum airflow across the heat sink of
70 CFM. Cooling should also be based on the whole system cabinet temperature not exceeding 45

o

C

(113

o

F), as well as providing good airflow across the Quad Amplifier heat sink.

The internal mounting options (Opt4 and Opt4A) are self-contained, stand alone packages. They include
cooling fans and a built-in shunt regulator, with internal shunt resistors for small motor loads of under 10
HP. To ensure long-term reliability, the ambient temperature of the cabinet should not exceed 45

o

C.

A X I S 1

A X I S 2

A X I S 3

A X I S 4

A X I S 1 & 2

A X I S 3 & 4

Q U A D A M P

( B O T T O M V I E W )

A C C - 8 F

AC

C-

8F

P M A C 2

M O T O R

C A B L E

M O T O R

C A B L E

M O T O R

C A B L E

M O T O R

C A B L E

E N C O D E R

S IG N A L S

E N C O D E R

S IG N A L S

J 1 0 J 9

Figure 2 Quad Amplifier Interconnection Diagram

Multiple Units

When more than one Digital Quad Amplifier is installed in a limited area, such as an electrical box,
always mount the amps side by side, and allow 3 inches (8 cm) between amplifiers. Do not stack the
Quad Amplifiers.

Vibration

When the Quad Amplifier is installed near a source of excessive vibration install an isolation device
underneath the Quad Amplifier.