Quad Amp Hardware Reference Manual

Installation

24

Figure 62 Soft Start Board Jumper, Potentiometer, Test Point, and LED Locations

Name Position

Description

Default

E1

1-2 jumper

Internal Power Supply Connection

2-3

open

JP6 Jumper

E-Stop

Configuration

JP7 Jumper

E-Stop

Configuration

Symbol`

Description

Tp Factory Set

Notes

R4 & TP5

High line fault set point

5.2/10.4 V

High line trips at 255/510 VAC

R2 & TP4

Over voltage fault set point

4.1/8.2 V

O/V trips at 410/820 VDC

TP3

Shunt IGBT turn-on set point

3.7V @ 230 VAC

Shunt turns on at 114% of the
nominal bus voltage

TP2

Main IGBT turn-on set point

2.75V @ 230VAC

Main IGBT turns on at 80% of
the nominal bus voltage

Note: Main and shunt set points are line sensitive and will vary with line voltage.

LED Symbol

Description

D25

L/LOW

Low Line, on when line voltage is below 30 VAC

D12

L/HI

High Line, on when line voltage is above 255 VAC

D7

GND

GND Fault, on if GND fault detected by Quad Amplifier logic board

D29

BIAS

Gate drive/bias fault, on if the gate drive supply fails

D27

OPEN

Open contacts fault, on when no main AC contactor auxiliary contacts are
not wired to QA or not working properly

D21

SHNT

Shunt, on when the shunt regulator is on

D22

RDY

Ready, on when no fault condition

D26

NOLINE

No Line, on when no 3-phase line present

D28

DSAT

De-saturation fault, on when current surge across the main IGBT or Shunt
IGBT is detected