Main ac input power, Control ac input voltage, For 120vac operation – Delta Tau 3Ax-602646-xUxx User Manual

Page 23: For 208vac operation, For 230vac operation, For 380 vac operation

Advertising
background image

Quad Amp Hardware Reference Manual

Installation

19

Figure 7 Quad Amp Main Circuit Wiring Diagram

Main AC Input Power

Connect desired main input power to input terminals marked L1, L2, and L3 (see Figure 7). The power
ground can be connected at the terminal marked CHAS GND or at the grounding screw, marked E, located
on the end panel of the Quad Amplifier chassis. The main input power terminals are rated for 600V and 85
Amps.

Control AC Input Voltage

Connect single-phase input power to pins 1 and 2 of AC input connector C3 marked CONTROL AC
INPUT PWR, located on the top panel of the Quad Amplifier (see Figure 7). Pin 4 of connector C3 is used
for ground (green wire). If the input power requirements have changed since the Quad Amplifier order, the
Control Power Transformer (T201), located under the Quad Amplifier cover, must be reconfigured for
proper operation (see Figures 7 and 8).

Note:

Control AC Input voltage is factory set in accordance with the ordering information.

For 120VAC Operation

Jump pin 1 to pin 5 and jump pin 2 to pin 6. Power is applied to pins 1 and 2 via AC input connector C3.

For 208VAC Operation

Jump pin 1 to pin 5 and jump pin 3 to pin 7. Power is applied to pins 1 and 3 via AC input connector C3.

For 230VAC Operation

Jump pin 1 to pin 5 and jump pin 4 to pin 8. Power is applied to pins 1 and 4 via AC input connector C3.

For 380 VAC Operation

Jump pin 4 to pin 5 and pin 6 to pin 9. Power is applied to pins 1 and 10 via AC input connector C3.