Flowserve M Slurry User Manual

Page 33

Advertising
background image

M SLURRY USER INSTRUCTION ENGLISH 71569241 - 02/08


Page 33 of 60

®

6.2.1 Routine inspection (daily/weekly)

The following checks should be made

and the appropriate action taken to remedy any
deviations:
a) Check operating behaviour. Ensure noise,

vibration and bearing temperatures are normal.

b) Check that there are no abnormal fluid or lubricant

leaks (static and dynamic seals) and that any
sealant systems (if fitted) are full and operating
normally.

c) Check that shaft seal leaks are within acceptable

limits.

d) Check the level and condition of oil lubricant. On

grease lubricated pumps, check running hours
since last recharge of grease or complete grease
change.

e) Check any auxiliary supplies eg heating/cooling (if

fitted) are functioning correctly.

Refer to the manuals of any associated

equipment for routine checks needed.

6.2.2 Periodic inspection (six monthly)

a)

Check foundation bolts for security

of attachment and corrosion.

b) Check pump running records for hourly usage to

determine if bearing lubricant requires changing.

c) The coupling should be checked for correct

alignment and worn driving elements.

Refer to the manuals of any associated

equipment for periodic checks needed.

6.2 3 Re-lubrication
Lubricant and bearing temperature analysis can be
useful in optimizing lubricant change intervals. In
general however, the following is recommended.

6.2.3.1 Grease lubrication

See section 5.2.2 for grease

recommendations.


Re-greasing quantities for each bearing are contained in
the table below. Please note that standard pumps are oil
lubricated. Grease only when factory installed grease
fittings are supplied.

Table 6.2.3.1 Bearing Regreasing Quantities

BRG. THRUST

BEARING

LINE

BEARING

FRAME SIZE

OZ.

CU. IN.

CU. CM.

OZ.

CU. IN.

CU. CM.

1 1 1.2 20 3 3.6 60
2 3 3.6 60 7 8.5 140
3 7 8.5

140

14

17.1

280

4 9 11.0 180 18 22 361

Note: Frame 5 & 6 pumps can not be greased


Regrease

- via grease nipples every 2 000 hours or

sooner depending on the severity of the application.

It is important not to under or over grease the bearings
as this will lead to over heating and premature failure.

a) Grease lubricated bearing housings have grease

nipples fitted in the bearing covers.

b) Move the axial seal ring back so the gap between

the pump shaft and bearing cover can be seen.

c) Connect grease gun to the nipple.
d) Press grease into the bearing housing until the

first signs of it appear in the gap between the
housing and shaft, then stop greasing.

e) V-rings should be seated at the proper distance

from the sealing surface to avoid overheating.

f) The maximum allowable operating temperatures

for anti friction bearings will vary from unit to unit,
depending on ambient and fluid temperature. The

rise above ambient should not normally exceed 55
°C (131 °F) or a combined maximum of 95 °C
(204

°F).

g) A continuously rising temperature or an abrupt

temperature rise indicates a problem. If these
symptoms occur, stop the pump immediately and
investigate the cause.

TIME

TEMP

ERAT

U

R

E

Grease change

- every 4 000 hours or sooner

depending on the severity of the application.

Advertising