Flowserve LPNV Worthington User Manual

Page 27

Advertising
background image

LPNV USER INSTRUCTIONS ENGLISH 87900031 – 06/14

Page 27 of 48

5.6 Starting the pump

a) Close discharge valve if valve is not already

closed, and then crack open to assure minimal
flow. (Do not start unit with fully closed valve).
On first starts care must be taken not to cause a
system water hammer.

b) Prepare the driver for start up in accordance with

the driver manufacturer's instructions.

c) Warm up pump (if applicable).

Avoid severe thermal shocks to the pump as the
result of sudden liquid temperature changes.
The pump must be preheated prior to start up.
Unless otherwise specified the thermal
temperature of the casing must be within 55 °C
(100 °F) of the temperature of the liquid to be
pumped at time of start up. Due to the heavy
metal sections, the casing will lag the liquid
temperature during such changes, and severe
temperature stresses and subsequent

misalignment of machined fits may result.
Preheating is accomplished by circulating a
small amount of hot fluid through the casing by
utilizing vents, drains or bypass from discharge.
Preheat pump slowly at a rate not to exceed 55
°C per hour (100 °F per hour).

d) Prime pump and ensure suction valve is open.

Ensure flushing and/or cooling/

heating liquid supplies (if required) are turned
ON before starting the pump.

Before starting or while operating

the pump, the casing and suction line must be
completely filled with the liquid being pumped.
The rotating parts depend on this liquid for
lubrication and the pump may seize if operated
without liquid.

e) Ensure pump re circulation line (if required) is

open, clear and free of obstructions.

f) Check that pump is vented by observing leakage

from casing vent (when fitted) and

seal piping

vent. Close vent (if fitted) when liquid is emitted.

g) If the pump is equipped with mechanical seal,

make sure seal piping is turned on.

h) Turn on cooling liquid and assure correct flow

exists as specified (to cooler, bearing coil etc. if
provided.).

i) Prepare the driver for start-up in accordance

with the driver manufacturer’s instructions.

j) Double check pump rotation by starting unit

momentarily. The direction of input shaft
rotation is counter clockwise when facing
pump shaft from coupling end. Ensure that
the pump coasts down to a gradual stop.

If pump stops abruptly when driver

is shut down, investigate for pump binding. Take
necessary remedial action before resuming
operation.

k) Start the driver and bring it up to speed quickly.
l)

As soon as the pump is up to rated speed slowly
open discharge valve. This will avoid abrupt
changes in velocity and prevent surging in the
suction line.

m) Perform the operating checks.

5.7 Operating checks

In the interest of operator safety the unit

must not be operated above the nameplate

conditions. Such operations could result in unit
failure causing injury to operating personnel.
Consult user instruction book for correct
operation and maintenance of the pump and its
supporting components.

Operation at low flows results in

pump heating the liquid. A bypass may be
required to prevent vaporization and subsequent
pump damage. Refer to local FLOWSERVE
branch to determine if a bypass is required.
Mechanical damage may result from continuous
operation at flows less than the specified
minimum continuous stable flow.

Immediately after start up, and frequently during
running check the following:

a) Check suction and discharge pressure gauges.
b) Check pressure gauges on each side of suction

strainer.

c) Regulate the amount of fluid circulated to

mechanical seal, if applicable

d) Check for excessive leakage at seal areas.
e) Check for unusual noises.
f) Verify lubrication: check oil level in bearing

housing. (Refer to Section 5).

Operation of the unit without correct

lubrication can result in overheating of the
bearings, bearing failures, pump seizures and
actual break-up of the equipment exposing
operating personnel to physical injury.

g) Check for vibrations.
h) Check for adequate flow of cooling water, if

applicable.

i)

Check for hot alignment: for services 55 °C ( 100
°F) and more above ambient, after unit has been
operated a sufficient period of time to reach
normal operating temperature and condition, the
unit is to be shut down and

a "HOT" coupling

Advertising