11 DIN Valve Troubleshooting Chart

Problem

Possible Cause

Corrective Action

Stem motion impeded 1. Overtightened packing.

1. Refer to proper maintenance instructions and readjust.

2. Service temperature is beyond operating limits of trim design.

2. Reconfirm service conditions and contact factory.

Excessive leakage

1. Improperly tightened bonnet flange bolting.

1. Refer to step 11 of “Reassembling the Body” section for

correct tightening procedure.

2. Worn or damaged seat ring.

2. Disassemble valve and replace or repair seat ring.

3. Worn or damaged seat or bonnet gasket.

3. Disassemble and replace gaskets.

4. Inadequate actuator thrust.

4. Check for adequate multi turn actuator,

reconfirm service conditions and contact factory.

5. Incorrectly adjusted plug.

5. Refer to step 9 of “Reassembling the Body” section for correct

plug adjustment.

6. Improper flow direction.

6. Refer to original specifications or contact factory.

Inadequate flow

1. Improper plug adjustment, limiting stroke.

1. Refer to step 9 of “Reassembling the Body” section for

correct plug adjustment.

2. Service conditions exceed trim design capacity.

2. Verify service conditions and consult factory.

Plug slams

1. Trim sized too large for flow rate

1. Install reduced trim.