Code switch

Temperature coefficient

Tk [%/°C]

4 5 6 7

OFF OFF

ON

OFF 1.9

ON

OFF

ON

OFF 2.0

OFF ON

ON

OFF

2.1

ON ON ON OFF 2.2
OFF OFF OFF

ON

2.3

ON

OFF OFF ON

2.4

OFF

ON

OFF

ON

2.5

ON ON OFF

ON

2.6

OFF OFF ON ON

2.7

ON

OFF ON ON

2.8

OFF ON ON ON

2.9

ON ON ON ON

3.0

Adaptation of the cell constant
The cell constant adjusted at our factory is a characteristic geometric quantity of the
equipment and influences the calculation of conductivity. However, during operation this
constant can drift, e. g. due to dirt accumulated on the measuring electrode. If the
indicated conductivity value deviates from the measured comparative value you can
correct the measurement result of the transmitter by re-adjusting the cell constant.

Depending on the deviation set code switches 8 or 9 to ON, the cell constant will then
change continuously. Observe the conductivity indication and when the indicated value
agrees with the comparison measurement set the switch back to OFF. Should an
adjustment not be possible remove the transmitter and clean the measuring surface.

To restore the factory setting of the cell constant - e. g. after cleaning the measuring
surface - set code switches 8 and 9 simultaneously to ON. After approx. 1 sec. switch back
to OFF. The factory setting is restored.

Code switch

Deviation of the indicated
conductivity

8 9 Function

non

OFF

OFF

No change

Indicated value < Measured comparative
value

ON

OFF

Cell constant increases

Indicated value > Measured comparative
value

OFF

ON

Cell constant decreases

ON ON Restores factory setting

Functional Test
Use code switch 10 for performing a functional test. A value is simulated which exceeds
the final control range value and a current output of 20 mA is provided.

Code switch

Functional test

10

OFF

Normal operation

ON

Simulation
Final control range value
exceeded

When the functional test is finished set code switch back to OFF.