Conductivity control range / actual value output – Flowserve LRGT16-1 Spector compact Conductivity Transmitter System User Manual

Page 18

Advertising
background image

Power consumption
3 W

Fuse
Electronic thermal fuse T

max

85 °C, hysteresis – 2 °C

Conductivity control range / Actual value output

Control range*)

[

µS/cm at 25 °C]

Current output

mA =

µS/cm

4 mA corresponds to

20 mA corresponds to

20 20

100 100
200 200
500 500

1000 1000
2000 2000
6000 6000

0.5

12000

0.5

12000

Adjustable via code switch. Max. load for actual value output 750

Ω.

*) Conversion µS/cm into ppm (parts per million)
1

µS/cm = 0.5 ppm

Measurement cycle
1 sec.

Accuracy
5 %, referred to measured conductivity without temperature compensation

Temperature compensation
linear, Tk adjustable via code switch, 0 %/°C, 1.6 - 3.0 %/°C in steps of 0.1 %/°C

Time constant T (measured acc. to DIN 3440)
Temperature: 9 sec.
Conductivity: 14 sec.