Flowserve StarPac II Control Valves User Manual
Page 36
Integer
Register
Attribute Description
Notes
30014
RO
ADC value being output by the position
feedback Hallpot.
Range -32767 to 32767.
30015
RO
ADC value being output by the process
temperature thermocouple.
Range 0 to 16383.
30016
RO
Flow state register.
0 = liquid choked
1 = liquid non-choked
2 = gas non-choked
3 = gas choked
30017
RO
Scaled percentage of full scale process
value for currently selected process
variable.
Range -20 to 120. Fixed scale.
30018
RO
Scaled liquid flow in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70465, 70467.
30019
RO
Scaled gas flow in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70469, 70471.
30020
RO
Scaled P1ISA in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70473, 70475.
30021
RO
Scaled P2ISA currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70477, 70479.
30022
RO
Scaled dP ISA in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70481, 70483.
30023
RO
Scaled process temperature in currently
selected engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70485, 70487.
30024
RO
Scaled auxiliary input.
Range 0 to 9999. Variable scale. Scalar
registers are 70489, 70491.
30025
RO
Scaled 4-20 mA command input.
Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.
30026
RO
Scaled stem position.
Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent..
30027
RO
Scaled setpoint command.
Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.
30028
RO
Alarm source register.
Bit field/Bit Meaning
0 = Setpoint error
1 = Positioner error
2 = Tripped condition
3 = Unused
4 = Unused
5 = Override status
6 = Sensor malfunction
7 = Hardware malfunction
StarPac II User Interface Manual
30