Integer
Register
Attribute Description
Notes
30029
RO
External 115V accessory A&B on/off
input status.
0 = A&B on. (BCD220)
1 = A off, B on (BCD 221)
2 = A on, B off (BCD 222)
3 = A&B off (BCD 223)
30030
RO
Device address.
Range 1 to 254.
40031
RW
Process pressure unit selector.
40 = psig
41 = psia
42 = kPa g
43 = kPa a
44 = kg/sq cm g
45 = kg/sq cm a
46 = bar g
47 = bar a
40032
RW
Liquid flow unit selector.
01= US gpm
2 = lpm
3 = lb/hr
4 = kg/hr
5 = cu m/hr
6 = bbl/d
7 = UK gpm
8 = custom units
40033
RW
Gas flow unit selector.
20 = lb/hr
21 = kg/hr
22 = scfh
23 = mscfd (million scfd)
24 = scfn
25 = scm/hr
26 = custom units
40034
RW
Actuator pressure unit selector.
40 = psig
41 = psia
42 = kPa g
43 = kPa a
44 = kg/sq cm g
45 = kg/sq cm a
46 = bar g
47 = bar a
40035
RW
Process temperature unit selector.
60 = deg C
61 = deg F
62 = deg R
63 = deg K
StarPac II User Interface Manual