Floating
Point
Register

Attribute Description

Notes

70253

RO

Output from position Hallpot in percent.

70255

RO

4-20 mA analog auxiliary signal input
percentage.

70257

RO

Setpoint to controller in selected units.

70259

RO

Selected process variable value in
selected units.

70261

RW

Measured mechanical stroke of valve.

Range 1.0E-3 to 100

70263

RW

Softlimit maximum percentage.

Range -20 to 120. System will not open
past this percentage.

70265

RW

Softlimit minimum percentage.

Range -20 to 120. System will not close
past this percentage.

70267

RW

Full scale auxiliary input percentage.

Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.

70269

RW

Full scale delta pressure (DPISA) in
selected units.

Range .1 to 1.0E9.. Value is used to
calculate the process variable percentage.

70271

RW

Full scale liquid flow in selected units.

Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.

70273

RW

Full scale gas flow in selected units.

Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.

70275

RW

Full scale upstream pressure (P1ISA) in
selected units.

Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.

70277

RW

Full scale downstream pressure (P2ISA)
in selected units.

Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.

70279

RW

Full scale process temperature in
selected units.

Range -500 to 5000. Value is used to
calculate the process variable percentage.

70281

RW

Process temperature in selected units
equal to 0% of process.

Range -500 to 5000. Value is used to
calculate the process variable percentage.

70283

RW

Percentage of position used to output
20 mA on analog output channel.

Range .1 to 1.0E3.

70285

RW

Percentage of position used to output
4 mA on analog output channel.

Range -20 to 120.

70287

RW

Percentage of auxiliary input used to
output 20 mA on analog output channel.

Range .1 to 1.0E3.

70289

RW

Percentage of auxiliary input used to
output 4 mA on analog output channel.

Range -20 to 120.

70291

RW

Delta P (DPISA) in selected units used to
output 20 mA on analog output channel.

Range .1 to 1.0E9.

70293

RW

Delta P (DPISA) in selected units used to
output 4 mA on analog output channel.

Range 0 to 1.0E9.

70295

RW

Liquid flow in selected units used to
output 20 mA on analog output channel.

Range .1 to 1.0E9.

70297

RW

Liquid flow in selected units used to
output 4 mA on analog output channel.

Range 0 to 1.0E9.