Flowserve StarPac II Control Valves User Manual

Page 50

Advertising
background image

Floating
Point
Register

Attribute Description

Notes

70459 RW

X

T

D2 curve fit coefficient.

Range -1.0E9 to 1.0E9.

70461 RW

X

T

E2 curve fit coefficient.

Range -1.0E9 to 1.0E9.

70463 RW

X

T

curve fit breakpoint.

Range 0 to 100.

70465

RW

Minimum liquid flow in selected units for
register 30018.

Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.

70467

RW

Maximum liquid flow in selected units for
register 30018.

Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.

70469

RW

Minimum gas flow in selected units for
register 30019.

Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.

70471

RW

Maximum gas flow in selected units for
register 30019.

Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.

70473

RW

Minimum upstream pressure (P1ISA) in
selected units for register 30020.

Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.

70475

RW

Maximum upstream pressure (P1ISA) in
selected units for register 30020.

Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.

70477

RW

Minimum downstream pressure (P2ISA)
in selected units for register 30021.

Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.

70479

RW

Maximum upstream pressure (P2ISA) in
selected units for register 30021.

Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.

70481

RW

Minimum delta pressure (DPISA) in
selected units for register 30022.

Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.

70483

RW

Maximum delta pressure (DPISA) in
selected units for register 30022.

Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.

70485

RW

Minimum process temperature in
selected units for register 30023.

Range -500 to 5000. Represents 0 for the
calculated integer process variable value.

70487

RW

Maximum process temperature in
selected units for register 30023.

Range -500 to 5000. Represents 9999 for
the calculated integer process variable
value.

70489

RW

Minimum auxiliary percentage for
register 30024.

Range -1.0E9 to 1.0E9. Represents 1000
for the calculated integer process variable
value.

70491

RW

Maximum auxiliary percentage for
register 30024.

Range -1.0E9 to 1.0E9. Represents 9999
for the calculated integer process variable
value.

70493

RW

Ramp rate for signature test in
percent/minute.

Range 10 to 150. Valve stem will move at
this rate during a ramp closed or ramp
open test.

StarPac II User Interface Manual