Integer
Register

Attribute Description

Notes

40081

RW

Reset integer scaler flag.

Range 0 to 1. Writing a value of 1 to this
register causes the device to recalculate
the scalers used to calculate the integer
process variables.

40082

RW

Start signature function flag.

Range 0 to 2.

0 = Function complete

1 = Ramp function

2 = Step function

40083

RW

Signature/logger data packet to be read.

Range 1 to 650.

40084

RW

Load signature data packet into
signature registers.

Range 0 to 1. Writing a value of 1 to this
register causes the device to load the
signature registers with the signature
packet requested in register No. 40083.

40085

RW

Load logger data packet into signature
registers.

Range 0 to 1. Writing a value of 1 to this
register causes the device to load the
signature registers with the logger packet
requested in register No. 40083.

30086

RO

Number of signature packets available.

Range 0 to 650

30087

RO

Number of logger packets available.

Range 0 to 650

30088

RO

Signature/logger accessory on/off status
register.

40089

RW

Variable number for process temperature
input to be used in flow calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
process temperature input to the flow
calculation; -1 disables.

40090

RW

Variable number for upstream process
pressure (P

1

) input to be used in flow

calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
upstream process pressure input to the
flow calculation; -1 disables.

40091

RW

Variable number for downstream
process pressure (P

2

) input to be used in

flow calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
downstream process pressure input to the
flow calculation; -1 disables.

40092

RW

Variable number for specific gravity input
to be used in flow calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
specific gravity input to the flow
calculation; -1 disables.

40093

RW

Variable number for molecular weight
input to be used in flow calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
molecular weight input to the flow
calculation; -1 disables.

StarPac II User Interface Manual