Check switching functions

Use the following table as reference when checking the individual switching functions.

Electrode rod 1 = low level 1

Electrode rod1 emerges

Relay 1 is de-energized after 1sec.

LED 1
illuminated

Electrode rod1 enters the
liquid

Relay 1 is energized after 1sec.

LED 1 off

Test and lock-out function

Press TEST button

Relay 1 is de-energized and locked out after 1sec.

LED 1
illuminated

Press RESET button for 3 s

Relay 1 is energized after 1sec.

LED 1 off

Electrode rod1 emerges

Relay 1 is de-energized and locked out after 1sec.

LED 1
illuminated

Electrode rod1 enters the
liquid
Press RESET button for
3sec.

Relay 1 is energized after 1sec.

LED 1 off

Electrode rod 2 = low level 2

Electrode rod2 emerges

Relay 2 is de-energized after 1sec.

LED 2
illuminated

Electrode rod2 enters the
liquid

Relay 2 is energized after 1sec.

LED 2 off

Electrode rod 4 = high level

Electrode rod4 enters the
liquid

Relay 4 is de-energized after 3sec.

LED 4
illuminated

Electrode rod4 emerges

Relay 4 is de-energized after 3sec.

LED 4 off