Malfunctions / troubleshooting, Fault finding list – Flowserve NRGS15-1 User Manual

Page 24

Advertising
background image

24

Malfunctions / Troubleshooting

Fault finding list

Switchpoint "Pump OFF" exceeded - no function

Fault:

Mains voltage is not applied.

Remedy:

Switch on mains voltage. Connect level switch according to wiring diagram
(Fig. 5).

Fault:

The electrical conductivity is too low.

Remedy:

Set code switch

to 0.5 µS/cm.

Fault:

The earth connection to the vessel is interrupted.

Remedy:

Clean seating surfaces (see Fig. 3) and insert metal joint ring

Ø 33 x 39

DIN 7603 (made from s. s. 1.4301). Do not insulate the level switch with
hemp or PTFE tape!

Fault:

Electronic circuit board defective.

Remedy:

Replace electronic circuit board.

Level below switchpoint "Low level" - no function

Fault:

The electrode tips have earth contact.

Remedy:

Check and, if necessary, change position of installation.

Fault:

If the equipment is installed inside the boiler: The vent hole in the protection
tube does not exist or is obstructed.

Remedy:

Check installation of level switch. Make sure that the level in the protection
tube corresponds to the actual water level (see Examples of Installation).

Switchpoint has been reached - incorrect function

Fault:

The switching function has not been assigned correctly. The electrode tips
have been cut to the wrong length.

Remedy:

Assign the electrode tips correctly and change connections on the electronic

circuit board

correspondingly.

Fault:

The switching function does not correspond to the selected function. The
code switch has been set to the wrong value.

Remedy:

Set code switch

according to the selected function.