Table 3.4 – status bit definitions, Table 3.4 – status bit definitions (continued), 2 modbus function code 02 (read input status) – Flowserve DDC-100 Modbus Direct-to-Host User Manual

Page 7

Advertising
background image

8

DDC-100 Direct-to-Host Programming Guide

FCD LMAIM4019-00

FCD LMAIM4019-00

DDC-100 Direct-to-Host Programming Guide

9

Table 3.3 – DDC-100 Coil Assignments, Modbus Function Code 01 Usage for Digital Outputs

Coil

Number

Bit

Number MX/DDC

UEC-3-DDC

DDC-100 Clamshell

I/O Module

1

00

Close / Stop

Close / Stop

Close / Stop

Do Not Use

2

01

Open / Stop

Open / Stop

Close / Stop

Do Not Use

3

02

AS-1

Lockout or Relay #3

Lockout or Relay #3

Relay #3

4

03

AS-2

Do Not Use

Relay #4

Relay #4

5

04

AS-3

Do Not Use

Relay #5

Relay #5

6

05

AS-4

Relay #6

Relay #6

Relay #6

7

06

AR-1 (Opt)

Do Not Use

Do Not Use

Relay #21

8

07

AR-2 (Opt)

Do Not Use

Do Not Use

Relay #12

9

08

AR-3 (Opt)

Do Not Use

Do Not Use

Do Not Use

Note 1: Relay #2 is physical Relay K2.
Note 2: Relay #1 is physical Relay K1.

Example
Poll field unit number 3 for 8 coils starting at coil 1.

Query 0301000000083C2E

Response 03010118503A

Message Breakdown

Query

Response

03

Slave (Field Unit) Address

03

Slave (Field Unit)

Address

01

Function

01

Function

00

Starting Address Hi

01

Byte Count

00

Starting Address Lo

18 1

Data (Coils 8 - 1)

00

No. of Points Hi

503A

Error Check (CRC)

08

No. of Points Lo

3C2E

Error Check (CRC)

Note 1: 18h equals 00011000 or coils 4 and 5 are ON.

3.2.2 Modbus Function Code 02 (Read Input Status)

This function code is used to read the discrete input status bits in the DDC-100 Field Unit. The use
of this function code will provide the user with the input status bits that are used to develop holding
registers 9 through 13. The status bit inputs are contained in locations 10129-10208 for each
DDC-100 Field Unit and are defined in Table 3.4.

Table 3.4 – Status Bit Definitions

Bit Number

Modbus

Bit

Address

UEC-3-DDC and DDC-100 Clamshell

I/O Module

129

128

Opened

Not Used

130

129

Closed

Not Used

131

130

Stopped

Not Used

132

131

Opening

Not Used

133

132

Closing

Not Used

134

133

Valve jammed

Not Used

135

134

Actuator switched to local mode

Not Used

136

135

Combined fault

Not Used

Table 3.4 – Status Bit Definitions (continued)

Bit Number

Modbus

Bit

Address

UEC-3-DDC and DDC-100 Clamshell

I/O Module

137

136

Over-temperature fault

Not Used

138

137

Actuator failing to de-energize

Not Used

139

138

Channel A fault

Channel A fault

140

139

Channel B fault

Channel B fault

141

140

Open torque switch fault

Not Used

142

141

Close torque switch fault

Not Used

143

142

Valve operated manually fault

Not Used

144

143

Phase error

Not Used

145

144

Input “open verify” is not active after open

command is initiated

Not Used

146

145

Input “close verify” is not active after close

command is initiated

Not Used

147

146

Input “open verify” is active after open

command is de-energized

Not Used

148

147

Input “close verify” is active after close

command is de-energized

Not Used

149

148

“Ph_det” (Phase Detect) input is active.

One or more phases is missing

Not Used

150

149

“Ph_seq” (Phase Sequence) input is active.

Reverse phase sequence is occurring

Not Used

151

150

Valve manually moved from mid-travel to

open

Not Used

152

151

Valve manually moved from open to

mid-travel

Not Used

153

152

Valve manually moved from mid-travel to

close

154

153

Valve manually moved from close to

mid-travel

Not Used

155

154

Network emergency shutdown (ESD) is

active

Not Used

156

155

Local emergency shutdown is active

Not Used

157

156

Field unit microprocessor has reset since

the last poll

Not Used

158

157

Wrong rotation

Not Used

159

158

Opening in local mode

Not Used

160

159

Closing in local mode

Not Used

161

160

Close contactor (interlocked)

Not Used

162

161

Open contactor (interlocked)

Not Used

163

162

Lockout or user, Relay 3

Relay 3

164

163

Local pushbutton switch LED (UEC-3)

Relay 4 (Clamshell)

Relay 4

165

164

Local pushbutton switch LED (UEC-3)

Relay 5 (Clamshell)

Relay 5

166

165

User, Relay 6

Relay 6

167

166

Close contactor (non-interlocked)

Relay 2 (K2)

168

167

Open contactor (non-interlocked)

Relay 1 (K1)

169

168

Field unit software vs. ID

Field unit software vs. ID

170

169

Field unit software vs. ID

Field unit software vs. ID

171-176

170-175

Field unit software vs. ID

Field unit software vs. ID

177

176

Remote switch

User Input 8

178

177

Thermal overload

User Input 9

Advertising