Table 3.5 – field unit register definitions – Flowserve DDC-100 Modbus Direct-to-Host User Manual

Page 9

Advertising
background image

12

DDC-100 Direct-to-Host Programming Guide

FCD LMAIM4019-00

FCD LMAIM4019-00

DDC-100 Direct-to-Host Programming Guide

13

Table 3.5 – Field Unit Register Definitions

Register

Number

Register Name

MX/DDC Meaning

UEC-3-DDC Meaning

1

Command

Registers 1 and 2 are write-only

registers used for Modbus Function

Code 06

Registers 1 and 2 are write-only

registers used for Modbus Function

Code 06

2

Argument

Registers 1 and 2 are write-only

registers used for Modbus Function

Code 06

Registers 1 and 2 are write-only

registers used for Modbus Function

Code 06

3

Analog Output

APT Scaled Output Value

(Default 0-100)

N/A

4

Analog Output

ATT Scaled Output Value1

(Default 0-100)

Average Torque

(version 2.00 and greater)

5

Analog Input

Main Power Value (Volts)

Analog Input 4

6

Analog Input

Analog Input 1 (Default 0-100) User

4-20 mA Input (Heavy Smoothing)

Analog Input 3

7

Analog Input

Analog Input 2 (Default 0-100) User

4-20 mA Input

Analog Input 2

8

Position

Valve Position, Scaled Value (Default

0-100) (0-100, 2-255, 0-4095)2

Valve Position, Scaled Value (Default

0-100) OR Analog Input 1

9

Status Register

(Field Units as

MOV - Motor-

Operated Valve)

16 Bits of Field Unit Status

16 Bits of Field Unit Status

Bit 0 Opened

Bit 0 Opened

Bit 1 Closed

Bit 1 Closed

Bit 2 Stopped

Bit 2 Stopped

Bit 3 Opening

Bit 3 Opening

Bit 4 Closing

Bit 4 Closing

Bit 5 Valve jammed

Bit 5 Valve jammed

Bit 6 Actuator switched to local

mode1

Bit 6 Actuator switched to local

mode

Bit 7 Combined fault3

Bit 7 Combined fault3

Bit 8 Over-temperature fault

Bit 8 Over-temperature fault

Bit 9 Future Implementation

Bit 9 Actuator failing to de-ener-

gize

Bit 10 Network Channel A fault4

Bit 10 Network Channel A fault

Bit 11 Network Channel B fault4

Bit 11 Network Channel B fault

Bit 12 Open torque switch fault

Bit 12 Open torque switch fault

Bit 13 Close torque switch fault

Bit 13 Close torque switch fault

Bit 14 Valve-operated manually

fault

Bit 14 Valve-operated manually

fault

Bit 15 Phase error

Bit 15 Phase error

9

Status Register

I/O Module only

(Non-Valve

Service)

N/A

16 Bits of Field Unit Status
Bits 0-9
Not Used
Bit 10 Network Channel A fault
Bit 11 Network Channel B Fault
Bits 12-15 Not Used

Table 3.5 – Field Unit Register Definitions (continued)

Register

Number

Register Name

MX/DDC Meaning

UEC-3-DDC Meaning

10

Fault Register

(Not Used for I/O

Module)

16 Bits of Field Status

16 Bits of Field Status

Bits 0-3 Not Used

Bit 0 Input “open verify” is not

active after open command

is initiated

Bit 4 One or more phases are

missing

Bit 1 Input “close verify” is not

active after close command

is initiated

Bit 5 Reverse phase sequence is

occurring

Bit 2 Input “open verify” is active

after open command is

de-energized

Bits 6-9 Not Used

Bit 3 Input “close verify” is active

after close command is

de-energized

Bit 10 Network emergency

shutdown is active

Bit 4 “Ph_det” input is active. One

or more phases are missing

Bit 11 Local PB emergency

shutdown is active

Bit 5 “Ph_seq” input is active.

Reverse phase sequence is

occurring

Bit 12 MX microprocessor has

reset since the last poll

Bit 6 Valve manually moved from

mid-travel to open

Bit 13 Local Stop

Bit 7 Valve manually moved from

open to mid-travel

Bit 14 Opening in local mode

Bit 8 Valve manually moved from

mid-travel to close

Bit 15 Closing in local mode

Bit 9 Valve manually moved from

close to mid-travel

Bit 10 Network emergency

shutdown is active

Bit 11 Local emergency shutdown

is active

Bit 12 Field Unit microprocessor

has reset since the last poll

Bit 13 Wrong rotation
Bit 14 Opening in local mode
Bit 15 Closing in local mode