Wiring

Bus cable, cable length and size

To connect the equipment use the supplied M2 connecting sockets.
Note that screened multi-cored twisted-pair control cable

is required as Bus line,

e. g. UNITRONIC

®

BUS CAN 2 x 2 x ...mm² or RE-2YCYV-fl 2 x 2 x ...mm².

Control cable assemblies (cable with plug and connector) of various lengths are available as add-on

equipment.
The cable length dictates the baud rate (data transfer rate) between the bus nodes, and the total power

consumption of the sensor dictates the conductor size.

Baud rate

Cable length

Number of pairs

and conductor size [mm²]

250 kBit/s

25 m

2 x 2 x 0.34

25 kBit/s

250 m

2 x 2 x 0.5

00 kBit/s

335 m

2 x 2 x 0.75

50 kBit/s

500 m

available on demand

(depends on bus configuration)

20 kBit/s

000 m

0 kBit/s

000 m

Wiring the connecting sockets

Wire the connecting sockets in accordance with the wiring diagram.

Wiring diagram URB 2

UNITRONIC

®

is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.

Fig. 5

3

2

3

4

5

1

2

1

5

4

Key
1 Screen
2 Voltage supply

24 V DC+

3 Voltage supply

24 V DC–

4 CAN data line C

H

5 CAN data line C

L

6 Terminating resistor 20 Ω