Glossary

– continued –

Cell constant (conductivity control):

The cell constant is a geometric quantity characteristic of the level electrode and is taken into account

when calculating the conductivity. However, in the course of time this constant may chance, e. g. due

to dirt deposits accumulated on the measuring electrode.

If a reference measurement yields a result that differs from the indicated conductivity value check the

temperature compensation first. Only if the temperature coefficient setting is no longer sufficient for a

correct compensation should you modify the cell constant. In this case change the cell constant until

the reading and the indicated conductivity agree.
24hour purging pulse (conductivity control):

To prevent blocking of the continuous blowdown valve a purging pulse is triggered when the mains

voltage is switched on. The continuous blowdown valve is actuated and opens for 2 minutes. After this

period the valve is motored into the CLOSED position where it remains for 2 minutes. Then the valve is

motored into the OPERATING position or into the required control position.

This process is repeated every 24 hours. During stand-by operation the time interval continues without

triggering off the purging pulse. Note that during the purging process the MIN limit is not active.

The 24 hour purging pulse can be switched ON or OFF.