Systematic fault finding procedure for system malfunctions

The sources of malfunctions occurring in CAN bus systems operating with several bus-based stations

must be analysed systematically since faulty components or incorrect settings can give rise to

negative interactions with intact bus devices in the CAN bus system. These unwanted interactions

can cause error messages in fully functional bus devices, which will make fault detection even more

difficult.
We recommend the following systematic fault finding procedure:

Malfunctions

– continued –

Step 1 (Start)

Detach terminal strips

in all Bus sensors.
Level electrode

Conductivity electrode

Pressure sensor

Temperature sensor

etc.

Step 3

Apply mains voltage

to bus devices

of the system

e. g. NRS ...

and

NRG ...

Step 2

Plug in terminal strip

of the sensor

of the system

e. g. NRS ...

and

NRG ... (electrodes)

System O.K.

Detach terminal strips

between bus devices

of the system

e. g. NRS ...

and

NRG ...

System Fault

Use fault-finding

list to identify

the fault(s)!

Cut off power supply

to the equipment!

Check

Use fault-finding

list to identify

the fault(s)!

Final test

Have all faults

been eliminated?

Check next system