Menu Control

– continued –

Switchpoints, proportional range

Note

The adjustment range of the respective switchpoint is limited by the switchpoints above

and below it as well as 0 % and 00 %.
For more information on the

proportional range X

p

(capacitance level control) see

chapter Glossary page 42.

Concerning:

Level control NRG 26-40 and NRR 2-40

. To set the individual parameters press button

. The activated item is shown in the symbol

bar.

2. To set the desired parameter turn the navigation

wheel and confirm the input by pressing the

navigation wheel. The background of the selected

item is flashing.

3. To enter a new value turn the navigation wheel

and confirm the input by pressing the navigation

wheel.

The flashing stops.

4. To obtain more available elements repeat items 2 and 3 and press button

.

Switchpoints, output 420 mA

Note

The adjustment range of the respective switchpoint is limited by the switchpoints above

and below it as well as 0°C and 650°C.

Concerning:

Temperature control TRV 5-40 and TRS 5-40

. To set the individual parameters press button

. The activated item is shown in the symbol

bar.

2. To set the desired parameter turn the navigation

wheel and confirm the input by pressing the

navigation wheel. The background of the selected

item is flashing.

3. To enter a new value turn the navigation wheel

and confirm the input by pressing the navigation

wheel.

The flashing stops.

4. To obtain more available elements repeat items 2 and 3 and press button

.

Device name

Measuring range

Switchpoints

Switching times

045%

1:

080 %

2:

060 %

W:050% XP:020%

3:

040 %

4:

020 %

Device name

Status report

Switchpoints

Output 4-20mA

Channel 1:
Temperature 4mA:
Temperature 20mA:

000 °C
000 °C

Channel 2:
Temperature 4mA:
Temperature 20mA:

000 °C
000 °C

Device name

Measuring range

Switchpoints

Switching times

045%

1:

080 %

2:

060 %

W:050% XP:020%

3:

040 %

4:

020 %

Device name

Status report

Switchpoints

Output 4-20mA

Channel 1:
Temperature 4mA:
Temperature 20mA:

000 °C
000 °C

Channel 2:
Temperature 4mA:
Temperature 20mA:

000 °C
000 °C