Basic Adjustments

CAN Bus

Node ID

All level and conductivity controllers and associated electrodes are interconnected by
means of a CAN bus using the CANopen protocol. Every item of equipment features an
electronic address (Node ID). The four-core bus cable serves as power supply and data
highway for high-speed data exchange.
The CAN address (node ID) can be set between 1 and 123.

The NRS 1-40 is configured at our works and ready for service with other GESTRA
system components without having to set the node ID.

If several systems of the same kind are to communicate in one CAN bus
network, be sure to assign one node ID for each individual system component
(e. g. controller). Refer to pages 24 and 25 for more details.

Wiring

– continued –

Tools

Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680

Note

The node ID 3* for the second level electrode NRG 16-40 must be
adjusted on site since the equipment features the factory set default
value 2 when delivered.

Factory setting

The switching controller features the following factory set default values:

Baud rate: 250 kb/s

Sensitivity: 0.5 µS/cm

Node ID: 001

Configuration: Operation with two level electrodes NRG 1...-40

Relay de-energizing delay: 3 s