System malfunctions – Flowserve NRS 1-40 User Manual

Page 17

Advertising
background image

17

System Malfunction 2

System Malfunctions

– continued –

LED 2 flashes slowly.

A system malfunction in level
electrode 2 was detected.

LED 2 flashes slowly

Fault:

The max. admissible temperature in the terminal box of the electrode
has been exceeded.

Remedy: Insulate electrode flange against thermal radiation.

LED 1 and 2 flashes slowly

Hold down button .

LED 1 and 2 flashes slowly.

Fault:

The electronic circuit board of the level electrode is defective.

Remedy: Replace the electronic circuit board of the level electrode 2.

LED 2 flashes slowly

Hold down button .

LED 2 flashes slowly.

Press button twice for a few seconds
to acknowledge the malfunction
messages.

The system will continue to work once
the causes of the system malfunctions
are completely eliminated.