System Malfunctions

– continued –

LED “Bus status” flashes slowly.

System Malfunction 6

LED flashes slowly

Fault:

Data transfer in CAN bus interrupted.

Remedy: The bus cables have to be connected correctly according to the wiring

diagram (observe polarity!).
Make sure that all end-of-line nodes are provided with 120

terminating

resistors.

Cut off power supply and re-start system after 5 sec.

Fault:

The baud rate of one or more nodes is not set correctly.

Remedy: Check baud rate settings of all bus nodes. The baud rates must be

identical. Refer to section “Annex” for more details.

Cut off power supply and re-start system after 5 sec.

Fault:

The overall length of the bus cable does not correspond to the selected
baud rate.

Remedy: Change baud rate settings of all nodes according to page Annex.

Cut off power supply and re-start system after 5 sec.