System malfunctions – Flowserve NRS 1-40 User Manual

Page 16

Advertising
background image

16

System Malfunction 1

System Malfunctions

– continued –

LED 1 flashes slowly.

A system malfunction in level
electrode 1 was detected.

LED 1 flashes slowly

Fault:

The max. admissible temperature in the terminal box of the electrode
has been exceeded.

Remedy: Insulate electrode flange against heat radiation.

LED 1 and 2 flashes slowly

Hold down button .

LED 1 and 2 flashes slowly

Fault:

The electronic circuit board of the level electrode is defective.

Remedy: Replace electronic circuit board of the level electrode 1.

LED 2 flashes slowly

Hold down button .

LED 2 flashes slowly.

The system will continue to work once
the causes of the system malfunctions
are completely eliminated.

The terminal strip of the NRS 1-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before fixing or removing the equipment.