Test cycle, Alarm – Flowserve NRS 1-40 User Manual

Page 13

Advertising
background image

13

Indicator LED 1 changes after 3 sec. from rapid
flashing to lighting

3 sec.

Press button for 3 sec.
LED 1 flashes rapidly and remains
permanently illuminated after 3 sec.

A low-level alarm is simulated for
electrode 1.

Press button briefly.

LED 2 flashes rapidly and remains
permanently illuminated after 3 s.

A low-level alarm is simulated for
electrode 2.

This test cycle is performed for the water-
level limiting system (two level electrodes).

NRS 1-40

Indicator LED 2 changes after 3 sec. from rapid
flashing to lighting

Test Cycle

– continued –

There are four different alarm conditions:

Low-level alarm for
water-level limiter
(one level electrode).

Low-level alarm for
water-level limiting system
(two level electrodes).

Alarm

Low-level alarm for water level limiter

LED 1 flashes rapidly.

LED 1 remains permanently illuminated after
the de-energizing delay.

Low-level alarm for water level limiting system

LED 1 and 2 flash rapidly.

LED 1 and 2 remain permanently illuminated
after the de-energizing delay.