System Malfunction 4

System Malfunctions

– continued –

LED 4 flashes slowly.

A malfunction in the level switch has
been detected.

LED 4 flashes slowly

Fault:

The electronic circuit board of the level switch is defective (e. g. output
relay).

Remedy: Replace level switch. Restart system.

LEDs 1 to 4 flash rapidly.

A general communication
malfunction has been detected.

System Malfunction 5

LEDs flash rapidly

Fault:

No communication between bus devices possible.

Remedy: Check wiring, node ID, baud rate setting and bus cable.

Cut off power supply and re-start system after 5 sec.

Fault:

No voltage across terminal 25, self-checking routine unsuccessful.

Remedy: Wire NRS 1-40 as first device in the safety chain.

Wire NRS 1-40 according to wiring diagram (ensure constant voltage
supply across terminal 25). Restart system.

Fault:

Voltage across terminal 26 and/or 30.

Remedy: Do not connect these terminals.