20

Nominal current value

Fuse

4.0 A

KLK D 4

5.0 A

KLK D 5

6.0 A

KLK D 6

7.0 A

KLK D 7

8.0 A

KLK D 8

Fuses

„Fuses“ Table: Excerpt of Suitable Fuses, e.g., Littelfuse Fuses

Nominal current value

Fuse

9.0 A

KLK D 9

10.0 A

KLK D 10

12.0 A

KLK D 12

15.0 A

KLK D 15

20.0 A

KLK D 20

Example: Maximum short circuit current (I

SC

) of the solar module = 5.75 A

According to the criteria for selecting the correct fuse, the fuse must have
a nominal current greater than 1.8 times and less than 2.4 times the short
circuit current:
-

5.75 A x 1.8 = 10.35 A

-

5.75 A x 2.4 = 13.8 A

The fuse that should be selected according to the ‘Fuses’ table: KLK D12
with 12.0 A nominal current and 600 V AC/DC nominal voltage.