Status diagnosis and troubleshooting

Status diagno-
sis and trou-
bleshooting

90x
Service codes of the Fronius String Control 250/25 logged by the Datalog-
ger or sent, depending on the settings
x ... identifies the measuring channel

Cause:

Unacceptable deviation of a measuring channel from
the set value
x = 1 ...Measuring Channel 1
x = 2 ... Measuring Channel 2
x = 3 ... Measuring Channel 3
x = 4 ... Measuring Channel 4
x = 5 ... Measuring Channel 5

Remedy:

Check string fuses, check solar module strings, check
Fronius Solar.access settings

Missing logging data during the day

Cause:

Solar Net is open (the ‘Connection’ LED on the Data-
logger lights up red)

Remedy:

WARNING! An electrical shock can be fatal. Danger from DC
voltage from solar modules.
-

Make sure that the input and output sides in front of the
device are not charged before making any connections or
settings.

-

Any and all connections and settings should only be carried
out by qualified electricians.

-

Follow the safety rules in these operating instructions.

Safety

(1)

-

Set jumper to manual restoration of the energy
supply

-

Check wires, connections and the supply:
the error can be found after the first Fronius
String Control 250/25 in the OUT direction for
which the ‘X’ LED (1) lights red or there is no
power supply