background image

4

Explanation of
symbols - instal-
lation position

U

DCmax

at an altitude of:

0 to 2000 m = 1000 V
2001 to 2500 m = 950 V
2501 to 3000 m = 900 V
3001 to 3400 m = 850 V

IMPORTANT! The inverter must not be installed or used at altitudes
above 3400 m.

Do not install the inverter:
-

in areas where ammonia, corrosive vapours, acids or salts are
present
(e.g. fertiliser stores, ventilation openings from cattle sheds, chemi-
cal plants, tanneries, etc.)

As the inverter generates low levels of noise at certain times, it should
not be installed close to living areas.

Do not install the inverter:
-

in places where there is an increased risk of damage from farm ani-
mals (horses, cattle, sheep, pigs, etc.)

-

in stables or adjoining areas

-

in storage areas for hay, straw, chaff, animal feed, fertilisers, etc.

Do not install the inverter:
-

in places and environments subject to heavy build-up of dust

-

in places and environments in which a heavy build-up of dust con-
taining conductive particles (e.g. iron chips) is likely

Do not install the inverter:
-

in greenhouses

-

in storage or processing areas for fruit, vegetables or winegrowing
products

-

in places used to prepare grain, green fodder or animal feeds

2000 m

2000 m

2500 m

=

L1

N

+

-

~

U

DCmax

=

1000 V

U

DCmax

=

900 V

3000 m

2500 m

3000 m

3400 m

U

DCmax

=

815 V

U

DCmax

=

750 V

> 3400 m

=

L1

N

+

-

~

NH

3

=

L1

N

+

-

~

=

L1

N

+

-

~

=

L1

N

+

-

~

=

L1

N

+

-

~

The inverter is designed to be installed vertically on a vertical wall or pil-
lar.