TB11 - Analog Input Connections

TB11 is used for monitor sensors or dc voltage. An industry standard for sensors is to produce a 4 to 20
milliamp (mA) output to represent a range from no signal to full scale signal, with 0 mA being an
indication of an error condition. A 250-ohm resistor will produce a 1 to 5 V dc signal when 4 to 20 mA
flows through it resulting in a signal that can be connected directly to the input, assuming it is not greater
than 5 V dc. For voltages greater than 5 V, a resistor voltage divider network must be installed to reduce
the voltage level present on the input.

Figure 4. Typical Analog Input Wiring Diagram