Specifications – GAI-Tronics 12578-002 Monitored Input Module (MIM) User Manual

Page 11

Advertising
background image

Pub. 42004-711L2B

Model 12578-002 Monitored Input Module (MIM)

Page 11 of 12

f:\standard ioms - current release\42004 instr. manuals\42004-711l2b.doc
01/09

Specifications

Electrical
Power requirements ..................................................................................... 9–15 V dc (12 V dc nominal)

Current draw ................................................................. 300 mA maximum @ 12 V dc (no ground faults)

Number of input loops ................................................................................................................... 8 loops

Maximum devices on input loop ................................................................................. Unlimited (Mode 1)

1 (Mode 2)

1 (Mode 3)

Unlimited (Mode 5 - Dry)

1 (Mode 5 – Wet)

Input/output................................................................................................................................. Power in

Power out

RS-485 in

RS-485 out

8 field inputs

Data communications .................................................................................................................... RS-485

RS-485 termination ........................................................................ On board when P2 jumper is installed

End-of-line device ........................................................................................................... 20 k

Ω (Mode 1)

5.1

k

Ω in series with 15 kΩ across contact (Mode 2)

5.1

k

Ω in series with 15 kΩ across contact (Mode 3)

None (Mode 5)

Field Inputs

Mode 1:

Contact closure resistance (activated) ............................................................................... 1 k

Ω maximum

Open Fault Detection....................................................................................................... Minimum 65 k

Ground Fault Detection .................................................................................... Less than 200

Ω to ground

Modes 2 and 3:
Contact closure resistance (Mode 2: activated/ Mode 3: de-activated) ............................... 3 k

Ω maximum

Open fault detection ........................................................................................................ Minimum 65 k

Ground fault detection ...................................................................................... Less than 200

Ω to ground

Wire-to-wire short fault detection ..................................................................................... Less than 200

Mode 5 (Dry)

Contact closure resistance............................................................................................... 900

Ω maximum

Mode 5 (Wet)
DC input voltage range............................................................................... 20–30 V dc (24 V dc nominal)

Limitations:

Cable limitations .................................................................................... 100

Ω maximum loop resistance