Mode 3: IDC Single Normally-Closed (N.C.) Switch

In this configuration, only one normally-closed dry contact closure may be installed per supervised line.
In this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and -), and
ground faults. When the contact closure is not active (closed), the 15 k

Ω is bypassed and the circuit sees

only the 5.1 k

Ω load.

Figure 4. IDC Single Normally-Closed Switch

When the contact closure is active (open), the loop appears as a 20.1 k

Ω load (15 kΩ in series with 5.1

k

Ω). This changes the value of the input and indicates to the MIM that the contact closure is active. If

there is a short across + and -, if either leg is grounded, or if a break occurs on either leg, the MIM
indicates that a fault has occurred.

N

OTE

: The terminating resistors are not included with the MIM. These resistors are included in a kit

(12509-003) that must be ordered separately.