Model 12578-002 Monitored Input Module (MIM)

Page 6 of 12

f:\standard ioms - current release\42004 instr. manuals\42004-711l2b.doc
01/09

Model 2: IDC Single Normally-Open (N.O.) Switch

In this configuration, only one normally-open dry contact closure may be installed per supervised line. In
this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and -), and ground
faults. When the contact closure is not active (open), the loop appears as 20.1 k

Ω load (15 kΩ in series

with 5.1 k

Ω). This appears on the input to the MIM and indicates a healthy loop. When the contact

closure is active (closed), the 15 k

Ω resistor is bypassed.

Figure 3. IDC Single Normally-Open Switch

The circuit then sees only the 5.1 k

Ω load. This changes the value of the input and indicates to the MIM

that the contact closure is active. If there is a short across + and -, if either leg is grounded, or if a break
occurs on either leg, the MIM indicates that a fault has occurred.

N

OTE

: The terminating resistors are not included with the MIM. These resistors are included in a kit

(12509-003) that must be ordered separately.