8 – flow configuration – Greenheck AMD-xx-TD Transmitter User Manual

Page 13

Advertising
background image

13

5.8 – FLOW CONFIGURATION

This Operator Menu selection is where all application specific data is entered to configure the Vari-Green for a
unique application. Typical data includes: Units of Measure, Duct Type and Size, Flow Type, Units and Conditions,
and Output Lockdown.

Note: The factory has entered data in this section based on customer supplied information. Data can be reviewed

and verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information
sheet provided separately. Review this information BEFORE making any changes as it can have a
significant effect on the operation of the Vari-Green.

1. While in Operator Menu, use UP or DN to scroll to:

2. Press ENT to enter Flow Configuration menu. Display will indicate:

3. Press ENT and display will indicate current setting of Units (U.S. or METRIC).

Flow

Configuration

Dimensional Units

Selection

Operator Menu

Dimensional Units

U.S.

Temperature Units

°F

Duct Shape

RECTANGULAR

Duct Height

XX.XX in.

Duct Width

XX.XX in.

Duct Diameter

XX.XX in.

Duct Area

XX.XX Sq. Ft.

Actual or Standard

ACTUAL

Site Elevation

0 Feet

Volume Units

ACFM

Design Full Range

XX,XXX ACFM

Maximum Full Range

XX,XXX ACFM

4

Output Lockdown

200 AFPM

Return to

MAIN MENU

Flow Configuration Menu

Operator Menu

- Dimensional Units Selection

- Temperature Units Selection

- Duct Shape Selection

- Duct Height Selection ¹

- Duct Width Selection ¹

- Duct Diameter Selection ²

- Duct Area Selection ³

- Actual or Standard Selection

- Site Elevation Selection

- Volume Units Selection

- Design Full Range Selection

- Output Lockdown Selection

- Return to MAIN MENU

- Operator Password Selection

Flow Configuration

- Display Configuration

¹ Available only if RECT ANGULAR or OVAL is

selected as Shape

² Available only if ROUND is selected as Shape.

³ Available only if OTHER is selected as Shape.

Default slection shown

U.S or METRIC

°F or °C

RECTANGULAR, ROUND,

OVAL, FAN INLET-SINGLE,

FAN INLET-DOUBLE, or

OTHER

0.00 to 300.00 in.

0 to 10,000 mm

0.00 to 300.00 in.

0 to 10,000 mm

0.00 to 325.00 Sq.Ft.

0 to 35,500 Sq. M.

Actual or

Standard

0 to 15,000 Feet

0 to 4,572 M.

See UNITS list for

available

selections

Design value

adjustable up to

maximum value.

0 to 5000 AFPM

0.00 to 300.00 in.

0 to 10,000 mm

4

Maximum Full Range is based

on the duct area.

Advertising