Greenheck AMD-xx-TD Transmitter User Manual

Page 35

Advertising
background image

35

Data Link Layer Options

(check all that are supported)

BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5Mb, ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s):

X

MS/TP Master (Clause 9), baud rates: 9600, 19200, 38400 (default), 57600, 76800
MS/TP Slave (Clause 9), baud rate (s):
Point-to-Point, EIA 232 (Clause 10), baud rate(s):
Point-to-Point, Modem (Clause 10), baud rate(s):
LonTalk (Clause 11), medium:
Other:

Networking Options

(check all that are supported)

Annex H.3, BACnet Tunneling Router over UDP/IP
BACnet/IP Broadcast Management Device (BBMD)
BBMD supports registrations by Foreign Devices

Router, Clause 6 - List all routing configurations (e.g. ARCNET-Ethernet, Ethernet- MS/TP, etc.)

Segmentation Capability

(check all that apply)

Segment requested suppported..............................Window Size:
Segmented responses supported............................Window Size:

Character Sets Support

(check all that apply)

X

ANSI X3.4
IBM™/Microsoft™ DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (ICS-4)
JIS C 6226

Indicating support for multiple character sets does not imply they can all be supported simultaneously.

If this product is a communication gateway, describe the non-BACnet equipment/network(s) the gateway supports.
- Not applicable
Include any additional information about the product’s BACnet capabilities relevant to interoperability.

List of any property value range restrictions
- Object_Name .......................... <32 bytes
- Object_Identifier ..................... Device Type only
- Number_Of_APDU_Retries .... 0-255
-APDU_Timeout ........................ 0-65535 milliseconds
- Vendor_Identifier .................... 0-65535 milliseconds
- System_Status

Copyright © 2014 Greenheck Corporation

Varigreen Thermal Air Flow, Rev. 1 April 2014