The Manual Management menu allows the user to manually control the I/O
of the controller. The user can manually input values for the analog inputs
and digital inputs. The user can also manually control the analog outputs
and digital outputs. EXTREME CAUTION should be used when manually
controlling the I/O.
It is highly recommended that manual control of the I/O
is done only with factory assistance. The controller’s safeties and lockouts
are bypassed by this manual management and should only be used as
a troubleshooting feature. If the controller is powered down, I/O Manual
Management is reset to off. Therefore, if using this troubleshooting feature, the
best way to clear manually input values is to power down the controller.

T

his

screen

is

an

example

of

a

manually

managed

TemperaTure

analog

inpuT

.

To manually control an analog input, change Manual Control to ON. Move
cursor to Manual position and alter value. The altered value will be displayed
below.
Similar screens exist for the remaining I/O. Contact the factory for more
details.

The BMS Config menu allows the user to view and alter BMS protocol settings.
If the BMS protocol is BACnet or Modbus, additional screens allow further
configuration. See below for details. To access the BMS Config sub-menu,
enter the service password (Default=1000).

T

his

screen

allows

The

user

To

selecT

The

bms

proTocol

. a

ll

bms

proTocols

require

a

communicaTions

card

insTalled

in

The

serial card

porT

,

locaTed

on

The

face

of

The

conTroller

.

If the protocol is BACnet MSTP or BACnet IP/Eth, the user can change
common BACnet parameters via the controller. The BACnet Plugin must be set
to YES.

T

his

screen

allows

The

user

To

adjusT

m

odbus

parameTers

.

This screen only appears if the selected BMS protocol is set to Modbus

.

The address is the Modbus address of the card installed in the SERIAL CARD
port located on the face of the controller. (Factory Default Address = 1).
The Baud Rate should be set to the BMS baud rate (Factory Default Baud Rate
is 9600).

I/O Manual Management

END OF OVERRIDE MENU

Press ENTER to go to

I/O Manual Management

menu.

Analog Input

Outside Temperature Manual

Control B01: ON
Manual Position

290

Value

84.2°F

BMS Configuration

Protocol:

BACnet MSTP

BACnet Plugin?

YES

MODBUS SETUP

Address:

1

Baudrate

9600

G.