Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Reference guide for the microprocessor controller

Advertising
background image

Program Features

The microprocessor controller offers improved control
through easy monitoring and adjustment of unit
parameters by way of a lighted graphical display and a
push-button keypad.

Pre-Programmed Operating Sequences

The controller has been pre-programmed to offer
multiple control sequences to provide tempered
air. Factory default settings allow for easy setup
and commissioning. The sequence parameters are
fully adjustable. Refer to the Sequence of Operation
beginning on page 2 for details.

BMS Communication

With the addition of an optional BMS Communication
card, the user can remotely adjust set points, view
unit status points and alarms. The microprocessor
controller is capable of communicating over several
protocols:

• BACnet® MSTP

• LonWork®

• BACnet® IP/Ethernet

• Modbus

See Points List on pages 36 and 37 for a complete list
of BMS points.

Internal Time Clock

The controller has an internal programmable time
clock, allowing the user to add up to seven different
occupancy schedules. The user may also add Holidays
for additional energy savings. The time clock option

Introduction

TAP v2.10
Version Date: 4/1/14

WARNING

Electrical shock hazard. Can cause personal injury
or equipment damage. Service must be performed
only by personnel that are knowledgeable in the
operation of the equipment being controlled.

also has morning warm-up capability for optional
comfort at the time of occupancy.

Alarm Management

The microprocessor controller will monitor the unit
conditions for alarm conditions. Upon detecting an
alarm, the controller will record the alarm description,
time, date, available temperatures, and unit status for
user review. A digital output is reserved for remote
alarm indication. Alarms are also communicated via
BMS (if equipped).

Occupancy Modes

The microprocessor controller offers three modes of
determining occupancy: a dry contact, the internal time
clock or the BMS. If in the Unoccupied mode the unit
will either be shut down, or will cycle on to maintain
adjustable unoccupied room temperature and humidity
set points.

Remote Display Panel (Optional)

A touchpad display panel allows for remote monitoring
and adjustment of parameters, allowing ease of control
access without going outdoors.

1

DDC Controller for Tempered Air Products

Reference Guide for the Microprocessor Controller

Please read and save these instructions. Read carefully before attempting to operate or maintain the product
described. Protect yourself and others by observing all safety practices. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.

®

®

Document 475595

Microprocessor Controller for

Tempered Air Products