rOubleshOOting
c
hart
Problem
Possible cause
Solutions
Actuator does not operate
Cams are depressing travel switch
Adjust cams to their correct positions
Override is engaged/shaft depressed Apply electricity to cancel manual
mode
Wiring is incorrect
Check wiring and power supply
Actuator has reached its thermal
Allow time to cool
shutdown temperature
Actuator operates in reverse
Field wiring is reversed
Rewire field wiring
directions
Actuator does not fully close valve
Limit switches are tripping
Readjust travel limit switches
(or open valve)
Valve torque requirement is higher
Manually override out of seat, try
than actuator output
angle seating or fit larger actuator
Voltage power supply is low
Check power source
Motor hums but does not run
Motor brake engaged
Check that brake is not obstructed
Corrosion inside unit
Condensation forming
Test heater wiring, should have
constant power supply
Water leaking into the unit
Check all seals and possible water
entry through conduit
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual