Application

Factory installed sleeves may need to be extended in the field. This supplement covers the following
applications:
• When the factory sleeve extends all the way through the rated barrier (Figure 1)
• When the factory sleeve ends in the plane of the rated barrier (Figure 2).
This supplemental installation instruction provides details for attachment of the sleeve extension. Consult
Authority Having Jurisdiction (AHJ) for approval.

Figure 1: Factory sleeve extends all the way

through the rated barrier.

Fire or Fire Smoke

Damper

Fire Rated Partition

Factory Sleeve

Minimum 1 in.

Overlap

Sleeve

Extension

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555 (Listing #R13317)

Standard 555S (Listing #R13447)

Document number 462103

INSTALLATION INSTRUCTION SUPPLEMENT

Sleeve Extensions

FD & DFD Series

1

1

/

2

Hour Curtain Fire Dampers

and

FSD Series

Combination Fire Smoke Dampers

Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’
(Part #452763)
or
‘Installation Instructions for FSD-XXX, DFD-XXX, CFSD-XXX,
SSFSD-XXX Series Fire & Combination Fire Smoke Dampers’
(Part #461336)
or
‘Installation Instructions for FD & DFD 150X Series Curtain
Fire Dampers’ (Part #453946) for additional details.

®

Notes

1. Sleeve extension must be same material and gage

as factory sleeve.

2. The inside dimensions of the sleeve extension must

be the same dimensions as the outside dimensions
of the factory sleeve.

3. Sleeve extension must overlap the factory sleeve a

minimum of 1 in. (25mm).

Factory Sleeve

Sleeve Extension

Connecting Joint of Sleeves

See notes 4,5, and 7

Fire or Combination Fire

Smoke Damper

Figure 2: Factory sleeve ends in the plane of the rated

barrier.

4. All four sides of the sleeve extension must be

attached to the factory sleeve. Attachments must
be spaced a maximum of 6 in. (152mm) on center
and a maximum of 2 in. (51mm) from corners. A
minimum of 2 attachments per side (8 per damper)
are required. One of the methods of attachment
shown below must be used.

- tack or spot welds
- #10 sheet metal screws
- 1/4 in. (6mm) bolts and nuts
- 3/16 in. (4.7mm) steel pop rivets