Greenheck Smoke Detector Supplement (463813) User Manual

Fsd, fsd-3xxv & ssfsd series, Cfsd series, Smoke dampers and

Advertising
background image

Refer to:
‘Installation Instructions for SMD, SMDR and SSSMD Series
Leakage Rated Smoke Dampers’ (Part #461338)
or
‘Installation Instructions for CFSD Series Corridor Ceiling
Dampers’ (Part #461335)
or
‘Installation Instructions for CFSD, FSD, DFD, and SSFSD
Series Combination Fire Smoke Dampers’ (Part #461336) and
FSD-3XXV series (Part # 461666) for additional details.

Installation Instruction

Supplement for

SMD, SMDR & SSSMD Series

Smoke Dampers and

FSD, FSD-3XXV & SSFSD Series

Combination Fire Smoke Dampers and

CFSD Series

Corridor Ceiling Dampers

with Factory Mounted Duct Smoke Detectors

Figure 2: Smoke detector mounting orientation for dampers

equal to or greater than 25 inches (635mm) in
height.

Figure 1: Smoke detector mounting orientation for dampers

less than 25 inches (635mm) in height.

Notes

1. Mininum air velocity for smoke detector operation is 100 fpm

(2.5 m/s). Maximum is 4000 fpm (20.3 m/s).

2. Since the smoke detector is not rated for use at velocities

below 100 fpm (2.5 m/s), local code may require an alternate
means of damper closure such as zone detection or
automated damper closure when the system fan is shut down.
The local authority having jurisdiction should be consulted
prior to the installation of the damper and smoke detector.

3. Holes on sampling tube must face into airstream.
4. Smoke detector specifications are:

Operating temperature range: 23°F to 131°F (-5°C to 55°C)

Operating humidity range: 10% to 93% R.H.

Operation voltage: 24 VAC/DC or 120 VAC

5. Refer to System Sensor, D4120 Installation and Maintenance

Instructions for further installation details.

6. Refer to System Sensor, D4120, Installation and Maintenance

Instructions for maintenance and field tests.

7. System Sensor

3825 Ohio Avenue

St. Charles, Illinois 60174

Phone: 1-800-SENSOR2
Fax: 1-630-377-6495
Website: http://www.systemsensor.com

DuctMate
Connector

1.5 x 1.5 in.
Retaining Angles

1.5 x 1.5 in.

Retaining Angles

DuctMate
Connector

5.75

6.00

Wall Maximum

15.00

24.00

11 in. "A" dimension

21 in. sleeve length

6.000 wall
maximum

Duct Breakaway

Connection (by others)

Height equal to

or greater than

25 inches

Accessory (OCI/RRL/TOR)

mounted externally on right-

hand side of damper.

Note: All actuators will be

externally mounted on the
right-hand side of damper

3 in. minimum to
allow for retaining
angle and duct
breakaway connection

Smoke detector

mounted

externally on

left-hand side of

damper

1.5 in. x 1.5 in.

16 ga. minimum

retaining angle

1.5 in. x 1.5 in.
16 ga. minimum
retainign angles

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555 (Listing #R13317)

Standard 555S (Listing #R13447)

Document number 463813

®