Installation – Desa CGS2718NA User Manual

Page 10

Advertising
background image

www.desatech.com

113101-01C

10

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

12"

8"

(A)

18"

8"

20"

14"

22"

17"

24"

20"

All minimum
distances are
in inches

Log Set
24" Model

18" Model

2

1/2

"

6"

8"

10"

IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 12.

If Using Mantel

You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombustible

material must extend at least 8 inches up (for all

models). If noncombustible material is less than

12", you must install the fireplace hood accessory

(24" model only). Even if noncombustible material

is more than 12", you may need the hood accessory

to deflect heat away from your mantel shelf. See

Figure 5 (see page 9), Figure 6 and Figure 7 (see

page 11) for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 12.

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances listed below, you

will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6).
Determining Minimum Mantel Clearance
when Using a Hood
If minimum clearances in Figure 6 are not met, you

must have a hood. When using a hood there are

still certain minimum mantel clearances required.

Follow minimum clearances shown in Figure 7,

page 11, when using a hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirement

of the national product standard.

Follow all minimum clearances

shown in this manual.

Figure 6 - Minimum Mantel Clearances Without Using Hood

Advertising