LOG SIZING REQUIREMENTS

Minimum Firebox Size

Log

Front

Rear

Size Height Depth Width Width*
18"

17"

14"

24"

20"

24"

17"

14"

28"

21"

MINIMUM FIREPLACE CLEARANCE

TO COMBUSTIBLE MATERIALS

Log Size

Side Wall

Ceiling

18", 24"

16"

42"

*Measured at 14" Depth
Carefully follow the instructions below. This will

ensure safe installation into a masonry, UL127-

listed manufactured fireplace or certified vent-free

firebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace

cabinet to any combustible material and wall

should follow diagram in Figure 4.

Example:

The face of a mantel, bookshelf,

etc. is made of combustible material and

protrudes 3

1

/

2

" from the wall. This combus-

tible material must be 4" from the side of the

fireplace cabinet (see Figure 4).

Note:

When installing your gas logs into

a manufactured firebox, follow firebox

manufacturerʼs instructions for minimum

clearances to combustible materials.

B. Clearances from the top of the fireplace

opening to the ceiling should not be less

than 42 inches.

Figure 4 - Minimum Clearance for

Combustible to Wall

*Minimum 16 inches from Side Wall

*

Example

INSTALLATION

Continued

NOTICE: Manual control heaters

may be used as a vented product.

If so, you must always run heater

with chimney flue damper open. If

running heater with damper open,

noncombustible material above fire-

place opening is not needed. Go to

Installing Damper Clamp Accessory

for Vented Operation, page 12.

Minimum Noncombustible Material
Clearances

If Not Using Mantel

Note:

If using a mantel, proceed to If Using

Mantel, page 10. If not using a mantel, follow the

information below.
You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombustible

material must extend at least 8" up (for all models). If

noncombustible material is less than 12", you must

install the fireplace hood accessory (24" model only).

See Figure 5 for minimum clearances.

Noncombustible
Material

Requirements for

Distance (A)

Safe Installation

12" or more

Noncombustible material okay.

Between 8"

24" Model: Install fireplace

and 12"

hood accessory (GA6050,

GA6052 or GA6053,see

Accessories, page 31).

18" Model: Noncombustible

material okay.

Less than 8"

Noncombustible material must

be extended to at least 8".

See Between 8" and 12",

above. If you cannot extend

material, you must operate

heater with flue damper open.

Heat Resistant
Material

(A)

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace