Installation

Figure 11 H*34DLL* Top Vent Venting Graph for wall mounted terminations,

See Figures 14, 14a, or 14b.

The Venting Graph:

Measure the vertical height from the fireplace hearth to the centre of

the termination and the horizontal run from the fireplace flue collar to

the wall flange of the termination. Plot on the Venting Graph Figure 11,

11a, 12, 12a or 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 114" and the horizontal

run to the wall flange of the vent termination is 144", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 42" and the horizontal

run to the wall flange of the vent termination is 90", this would

NOT be an

acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 66" and

the horizontal run to the wall flange of the vent termination is 150",

this would NOT be an acceptable installation.

Section 3-3-1:

VENTING LAYOUT: Wall mounted termination.

Selection of components and details of venting layout should

adhere to the following guidelines:

„

Vent terminations must not be recessed in walls or siding.

„

For Heat Shield Requirements see Section 3-3-3.

„

Once the proposed venting layout has been determined, refer to

Figure 11, 11a, 12, 12a, 13, 15, 16, or 17 to ensure the layout

is acceptable.

Notes Wall Mounted Terminations: TOP VENT

„

All measurements for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graphs,

Figure 11, 11a, 12, 12a or 13.

Figure 12 H38DLL* Top Vent Venting Graph for wall mounted terminations,

See Figures 14, 14a, or 14b.

Figure 12a H38DLN* Top Vent Venting Graph for wall mounted terminations,

See Figures 14, 14a, or 14b.

Figure 11a H*34DLN* Top Vent Venting Graph for wall mounted terminations,

See Figures 14, 14a, or 14b.

36”

38”

B

C

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

A

72”

42”

B

C

A

Unacceptable vent run

within shaded area.

If your installation does not fall

within the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

Acceptable vent run

within non-shaded area.

72”

B

C

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

A

38”

36”

42”

B

C

A

Unacceptable vent run

within shaded area.

If your installation does not fall

within the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

Acceptable vent run

within non-shaded area.