H-Series DL Indoor Gas Fireplace

Page 18

XG0140 - 070714

Installation

Section 3-3-3: Heat Shields

Installing a Wall Mounted RHS7/RHS8 Heat shield

The RHS7/RHS8 Heat shield CANNOT be used when the Termination is

WITHIN 36" horizontal or 60" vertically from the fireplace, or directly off

the rear of the fireplace, as shown figure 20a. The RHS100/RHS101 Heat

Shield (Figure 21 and 21a) MUST be used within the noted dimensions.
To install the RHS7/RHS8, frame an opening in combustible construction,

Figure 20 below. Slide the Heat shield in place over the vent pipe which

attaches to the fireplace. After the fireplace and vent pipe has been

installed, clearances should match the dimensions in Figure 20.
Note: RHS7 is for H*34DL* models only. RHS8 is for H38DL* and

H42DL* models only.

Figure 20. RHS7 / RHS8 Installation. (Install by sliding over vent pipe where it

passes through the combustible construction).

Figure 21. RHS100 / RHS101 Installation. (Install by sliding Outer Section over

vent pipe where it passes through the combustible construction.

Figure 21a. Heat Shield. After sliding the outer section in place.

Installing a Wall Mounted RHS100/RHS101 Heat shield.

The RHS100/RHS101 Heat shield MUST be used where the RHS7/RHS8

Termination (Figure 20 and 20a) CANNOT be used. Use the RHS100/

RHS101 where any of the dimensions are within the parameters

shown, figure 20a.
To install the RHS100/RHS101, Slide the Inner Section over the vent

pipe that will connect to the fireplace. Fasten the vent pipe to the back

of the fireplace with a Min. of three sheet metal screws.
Next, slide the RHS100/RHS101 outer section from the outside of the

structure, see Figure 21.
To complete the installation fasten the Heat Shield Outer Section &

Termination frame to the structure Figure 21a.
Note: RHS100 is for H*34DL* models only. RHS101 is for H38DL* and

H42DL* models only

Figure 20a. RHS7 / RHS8 Installation. (Minimum requirements).

Figure 21b.

RHS100 / RHS101 Installation.

RHS8 Heat Shield

RHS7 or

1” Min. Both sides Typical

1” Min.

1” Min.

Combustible Framing

Combustible

framing

Termination

Drywall / sheetrock
RHS100 or RHS101 Heat Shield

Outer Section

Vent pipe, from fireplace

RHS100 or RHS 101 Heat Shield

Inner Section

Termination

Drywall / sheetrock

Outer Section

RHS100 or RHS101 Heat Shield

RHS100 or RHS 101 Heat Shield

Inner Section

RHS8 Heat

Shield

36” Min

RHS7 or

60” Min

Outer Shield

3/8” Min. Both sides Typical

3/8” Min.

3/8” Min .

Combustible Framing

Inner Shield