Installation – Montigo H34DL User Manual

Page 7

Advertising
background image

H-Series DL Gas Fireplace

Page 7

XG0140 - 070714

Installation

Clearances

When installing a shelf over the top of the fireplaces, the following

guidelines must be adhered to:

Rear Vent applications, the minimum clearance is 2" from the rear of

the fireplace to a wall, or any combustible materials, and 9" clearance

from the top of the fireplace to the underside of any combustible shelf

materials.

Top Vent applications, the minimum clearance is 2" from the rear of

the fireplace to a wall, or any combustible materials, and 17 1/2" to the

underside of any combustible shelf materials, Figure 4.

Top or Rear Vent applications where the Minimum mantel height is

required above the fireplace, (for an alcove or low profile shelf), ALL

Materials MUST BE NON-COMBUSTIBLE, Figure 5. The minimum

clearance is 2" from the rear of the fireplace to a wall, or any combustible

materials.

1” clearance is maintained on sides and bottom of vent runs and 2”

above horizontal vent runs to any combustible material.

The fireplace clearances are shown below:

H*DL*

9

17 1/2 2 1

0

4

MODEL

Top - Rear V

ent

Top - Top V

ent

Rear

Sides

Floor

Mantel

Installing The Standoffs

To avoid elevated mantel temperatures, all H*DL*- Series gas

fireplaces are required to have the supplied standoffs installed.

The fireplace is supplied with two standoffs. Bend and install these

standoffs on top of the fireplace ensuring that the height of the standoff

maintains a 6" clearance.

Figure 6. Installing the standoff's.

6"

Installing the Nailing Flange Extension - HC34DL* Only
Once the fireplace is placed into the rough framed opening, the supplied

nailing flange extension (Part No. HC34074) must be fasten securely

into place, with nails or wood screws. as shown in Figure 7.

3”

6”

Front View Side View

Figure 6a. Installing the Nailing Flange Extension.

The supplied nailing flange extension must be placed along the top

edge of the fireplace and securely fastened in place to the combustible

wood framing.

Note: The nailing flange extension can be substituted with a piece of

NON-Combustible material of the same size and thermal characteristics,

ie: cement board or equivalent. This is recommended in applications

where the facing materials will not adhere to the metal nailing flange.

Note: Clearance from top of fireplace to a combustible ceiling within

the fireplace enclosure.