Installation – Montigo MW34 DV User Manual

Page 7

Advertising
background image

Page 7 of 21

W3400 Gas Fireplace

Installation

Figure 10. Extended Installation using a combination of solid and

flex venting. Use the vent graph to determine your
allowable run, then select appropriate components.

Figure 11. Retracted Installation using a combination of solid and

flex venting. Use the vent graph to determine your
allowable run, then select appropriate components.

Figure 12. Horizontal flex installation.

Hearth

Termination

Exterior
Wall

3' max.

Flex Section

Hearth

Flex Section

Termination

Exterior
Wall

126"

30" Max.

Solid Section w/
90° Elbow

Heat
Shield

Heat
Shield

W3400T

Hearth

Flex Section

Solid Sections

Termination

Exterior
Wall

Heat
Shield

150" max.

30" max.

Example 1:

For our shortest venting configuration use components A
and F

(see Figure 9a)

.

Figure 9a. Typical Top Vent installation. If the 90° elbow is installed

directly on the fireplace, the height to the center of the
termination is 44".

Horizontal Venting

Figure 9b. Typical Top Vent installation. The solid sections can be

used in various combinations to obtain the desired vent
run. The vent run
must fall within the limits set by the
venting graph.

90° Elbow

MEXT Section

Heat Shield

Example 2:

A 10' section and elbow used in conjunction with 3 ft. flex section (PFL-
3) will, when extended in a five foot chase, allow for a maximum
horizontal run of twelve and one-half feet from the centre of the
fireplace to outside wall and a minimum of 8' when retracted in opposite
direction (see Figure 10 and 11).

"D" flex sections and "E" solid sections may be used in conjunction with
one another to obtain different possible horizontal length installations.
NOTE: Flex section must not exceed maximum horizontal length of 3
feet. (see Figure 12).

Termination

PEL-90 Elbow

PTKO Termination

Advertising