Installation, B. vertical (through-the-roof) installations – Montigo MW34 DV User Manual

Page 8

Advertising
background image

Page 8 of 21

W3400 Gas Fireplace

Storm collar

Support ring

PEXT
Solid Section

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Firestop

2' min.

PXT-10

Adaptor

PEXT

Flue

Collar

2' min.

Storm collar

Support ring

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Installation

B. Vertical (Through-The-Roof) Installations

Vertical Terminations must be installed:

minimum 2' (two feet) above the highest point where
vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 3' (three feet) from a parapet wall.

Maximum vent height is 20 feet above fireplace.
Note: Flame characteristics will change if the maximum vent
height is used.

Minimum clearances 1" from vent to all combustible materials
must be maintained.

Figure 13. Straight, vertical venting using required PXT-10 adaptor.

A maximum of two offsets with 90° bends may be made and shall not
exceed total length of 25% of the vertical vent height, when measured
center to center of piping.

Example: Typical vent installation.

20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed

This venting configuration meets requirements.

A - Termination

PVTK-1

B - Flex sections

PFL-1 (12" section)

PFL-2 (24" section)

PFL-3 (36" section)

PFL-4 (48" section)

C - Solid sections

PEXT-1 (12" section)

PEXT-2 (24" section)

PEXT-3 (36" section)

PEXT-4 (48" section)

D - Support Ring & Plate

PSPXT-8 (7" dia.)

E - Firestop

PS-8 (7" dia.)

F - Roof Flashing

PRF-7 (1/12 - 7/12 pitch)

PRF-12 (7/12 - 12/12 pt.)

PRF-16 (12/12 - 16/12 pt.)

Figure 14b. Vertical venting with 2 offsets.

Figure 14a. Vertical venting with 1 offset.

2' min.

2'

Storm collar

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support straps or
support plate & ring

Firestop

Firestop

Firestop

Support plate
& ring

35' max.

35' max.

Top Vent

35' max.