9 | LS Installation Manual

Figure 9: Multiple Distributor Humidifier with Multiple Traps

6 Follow the steps listed in “Installation Of LiveSteam Humidifier” section to complete

installation.

Installation Of Livesteam Humidifier

Note: Follow all general instructions provided with valve and actuator.
To complete installation follow the steps listed below.

1 Steam outlets of distributor should face into the air stream unless distributor is insulated.

Nortec’s standard is right face.

2 Distributors must be mounted level. There is a support bracket at the end of the distributor

to secure to the duct wall. See Figure 11 to 14 for installation tips.

3 The steam distributor in a Single Distributor Humidifier should be centered in the duct.
4 The steam distributor should be mounted in a straight section of duct. Please consult your

Nortec agent if absorption distance is a problem. For calculation of absorption distance
please refer to Nortec manual Form #163D.

5 Do not locate the steam distributor within 10 feet of high efficiency filters, otherwise the

filter will become saturated.

6 Cut a hole in the side of the duct large enough to insert the steam distributor. Duct plates

are provided to seal any opening.

7 Install actuator. During installation follow instructions shipped with actuator.
8 For ease of maintenance, provide shut-off a valve before humidifier (between strainer and

steam main). It can also be used to minimize heat gains during the non-humidification
period.

9 Install strainer before entering system and steam trap. Connect to steam and condensate

return mains.