Mini sam-e with pressurized steam, Mini sam-e pressurized with external separator – Nortec LiveSteam v.2 User Manual

Page 30

Advertising
background image

27 | LS Installation Manual

Mini SAM-e with Pressurized Steam

Mini SAM-e Pressurized with External Separator



Strainer

Manual Shut-Off
Valve (By Others)

Steam Main

F & T Steam Trap

Separator

Actuator & Valve

Pressurized condensate
return main

1” Air Gap

Drain

Steam from top of main

Manual Shut-Off
Valve (By Others)

6” min.

6” min

Return to non-pressurized
condensate return main

Duct Width

Duct

Height

Duct Floor

Mounting
bracket

• Steam components in grey are provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from separator to be returned to pressurized condensate main.
• Condensate from SAM-e to be returned to atmospheric floor drain.

When pressurized steam enters the SAM-e, the pressure drops down to almost atmospheric
pressure. Therefore, it must be drained atmospherically, and the use of a condensate pump
(rated for 212ºF) must be used to raise the condensate to a higher elevation.